The Johnson Controls A28AK-2 Flange Mounted Differential Duct Thermostat is a thermostat that is used in HVAC systems that need fine tuning. The two-stage flange-mounted thermostat guarantees stable climate control in ducted systems through the temperature range of 60°F to 130°F with a differential of 2°F. Its 2-SPDT switch type makes it strong enough to switch between cooling and heating modes depending on the set temperature limits. Since it is well built to provide long-term dependability and performance like air handling units and ventilation systems, this thermostat is vital for maintaining the appropriate temperature.
https://www.partshnc.com/media/catalog/product/a/2/a28ak-2.jpg

Specifications

  • Temperature Range: 60°F-130°F
  • Type: Two-Stage Flange-Mounted Differential Duct Thermostat
  • Switch Type: 2-SPDT
  • Differential Temperature: 2°F
  • Weight: 1.86lbs

Product Overview:
Controls duct-air temperature through two-stage electromechanical switching. The Johnson Controls A28AK-2 is a flange-mounted duct temperature control designed to operate separate control circuits in response to changes in air temperature. Its air-coil sensing element and dual-switch arrangement support staged temperature control in HVAC air-handling applications.

Air Temperature Sensing:
The control uses a specially designed liquid-filled air-coil sensing element to detect changes in duct-air temperature. Its flange-mounted arrangement allows the sensing element to be positioned at an appropriate insertion depth within the airstream. The element support bracket helps maintain its position where airflow velocity is high.

Two-Stage Switching:
Operates two independent SPDT snap-action switches to provide separate high- and low-stage control. As duct temperature changes, the switches change contact state according to their configured action, allowing separate control circuits to respond at their respective thresholds. This arrangement supports staged operation rather than a single switching point.

Replacement Guidelines:
Replace the Johnson Controls A28AK-2 duct temperature control when a confirmed fault prevents accurate temperature response or reliable operation of either switching stage. Have a qualified HVAC technician inspect the sensing element, switch contacts, wiring, and mounting arrangement before replacement. The control is intended for operating control, not as the sole safety limit.

Common Failure Symptoms:

  • Duct temperature control does not respond to changes in air temperature.
  • One or both switching stages fail to operate.
  • Connected equipment does not respond at the intended temperature threshold.
  • Temperature control becomes inconsistent or unreliable.
  • The sensing element or mounting assembly shows visible damage.
  • Switch contacts fail to change state reliably.

Equipment Compatibility:
The A28AK-2 is designed for duct temperature control applications in rooftop units, make-up heaters, duct heaters, and air-handling systems. Confirm the existing control's two-stage switching arrangement, sensing-element configuration, mounting requirements, and operating range before ordering.

Technical Specifications:
Brand: Johnson Controls
Part Number: A28AK-2
Series: A28
Component Type: Duct temperature control
Control Type: Two-stage
Switch Configuration: Two SPDT snap-action switches
Mounting Type: Flange-mounted
Temperature Range: 60°F–130°F
Differential per Stage: 2°F
Between-Stage Differential: 3°F

Write Your Own Review
You're reviewing:Johnson Controls A28AK-2 2-SPDT Duct Thermostat 60°-130°F Flange Mounted 2°F Differential
Your Rating
Customer Questions
What is the Johnson Controls A28AK-2 duct temperature control used for?

It monitors duct-air temperature and operates two separate control circuits through its two-stage switching arrangement.

How do the two SPDT switches function?

Each switch provides a separate changeover contact arrangement, allowing the control to operate independent high- and low-stage circuits.

How is the sensing element positioned inside the duct?

The adjustable mounting flange allows the sensing element to be inserted at an appropriate depth in the airstream.

What is the difference between the stage differential and the between-stage differential?

The 2°F differential applies to each individual stage, while the manufacturer lists a separate 3°F differential between stages.

When should this duct temperature control be replaced?

Replace it when a confirmed fault prevents reliable temperature sensing or operation of either switching stage.