Product Overview:
Refrigerant pressure monitoring and compressor control are central to the role of the Johnson Controls P70MA-18 Dual Pressure Control. This OEM control component monitors low-side and high-side pressure through separate sensing mechanisms and operates electrical contacts in response to changing pressure conditions. Its dual-pressure switching arrangement supports compressor circuit protection, while the manual reset function allows controlled restoration after a high-pressure trip.
Dual Pressure Monitoring:
Monitors suction-side and discharge-side pressure through separate pressure-responsive mechanisms. The low-pressure section responds to changes in suction pressure, while the high-pressure section monitors discharge pressure. These independent functions support compressor pressure management during refrigeration system operation.
Electrical Switching:
Uses an SPST switching arrangement to control the connected electrical circuit according to pressure conditions. The high-pressure side incorporates a manual-reset lockout mechanism that prevents automatic restoration after a high-pressure cutoff. The low-pressure section provides pressure-responsive switching with an adjustable differential. This arrangement supports coordinated pressure control and compressor shutdown under designated operating conditions.
Replacement Guidelines:
Replace the Johnson Controls P70MA-18 Dual Pressure Control when functional testing confirms that it no longer responds accurately to pressure changes or switches the connected electrical circuit reliably. Replacement may be necessary if the low-pressure control fails to operate at its intended settings, the high-pressure section does not provide reliable cutoff, or the manual-reset mechanism becomes defective. Have a qualified refrigeration technician inspect the pressure connections, capillary assembly, electrical contacts, and compressor control circuit before replacement.
Common Signs of Failure:
Compressor operation stops unexpectedly due to inconsistent pressure switching.
Pressure control fails to respond to changing refrigerant conditions.
Manual reset operation becomes unresponsive.
Capillary tubing develops visible damage.
Electrical contacts fail to switch consistently.
Equipment Compatibility:
The P70MA-18 belongs to the Johnson Controls PENN P70 dual-pressure control series. It is designed for commercial refrigeration and air-conditioning applications using non-corrosive refrigerants. Its low-pressure adjustment, high-pressure manual-reset function, and capillary pressure connection are important selection characteristics. Confirm the required pressure settings, refrigerant application, connection arrangement, and electrical contact requirements against the original equipment documentation before installation.
Technical Specifications:
Brand: Johnson Controls
Part Number: P70MA-18
Product Type: Dual Pressure Control
Connection Length: 12 Inches
Low Pressure: 80 PSI
High Pressure: 100–425 PSI
Reset Type: Manual Reset (M/R)
Capillary Length: 36 Inches