Johnson Controls V47AR-2 Temperature Actuated Modulating Valve 115°F-180°F 1-1/2"
Specifications
- Temperature Range: 115°F to 180°F
- Pipe Connection Diameter: 1-1/2"
- Material: Stainless Steel
- Weight: 15.13lbs
Loyalty ProgramPRODUCT OVERVIEW:
Temperature actuated water regulating valves manage cooling liquid flow using remote thermal sensing. The Johnson Controls V47AR-2 Temperature Actuated Modulating Valve is an OEM component designed to provide automatic flow control in compatible water-regulated systems. Operating without external electrical power, this direct-acting valve adjusts internal fluid passages as temperature shifts at the sensing bulb. By modulating water throughput across a 115°F to 180°F range, the unit maintains system thermal stability and protects equipment from temperature excursions.
REMOTE THERMAL SENSING:
Thermal fluid expansion inside the remote sensing bulb drives internal valve positioning through an armored capillary tube. As temperature rises at the sensing bulb, expanding liquid generates hydraulic force that travels down the capillary line to position the valve seat. The direct-acting mechanism opens further under higher heat loads to allow maximum cooling water flow through the 1-1/2" valve body. When temperatures drop back toward setpoint, internal spring force balances the fluid pressure to throttle water throughput.
HEAVY-DUTY FLOW REGULATION:
Constructed with a heavy-duty cast iron body, the valve provides long-term structural durability in continuous fluid handling applications. The internal direct-acting mechanism connects to the thermal element, modulating water passage across the 1-1/2" ASME flanged connection ports. This self-contained assembly maintains precise flow regulation strictly in response to thermal conditions at the 1/2" NPT bulb mounting point, ensuring steady operation under fluctuating equipment loads.
REPLACEMENT GUIDELINES:
Component replacement is necessary when the valve fails to adjust water flow, displays seat binding, or suffers capillary charge loss. Malfunctioning temperature regulating valves compromise system performance by causing temperature overshooting, inadequate heat dissipation, or continuous fluid waste. Qualified technician assistance is recommended for hydronic line piping, pressure testing, and thermal bulb installation. Before purchasing, verify the part number and all relevant specifications against the original equipment documentation to ensure the replacement matches the system requirements.
COMMON FAILURE SYMPTOMS:
EQUIPMENT COMPATIBILITY:
The Johnson Controls V47AR-2 is intended for compatible water and heating equipment requiring a 1-1/2" ASME flanged direct-acting temperature regulating valve with a Style 4 bulb and a 115°F to 180°F temperature range. Confirm the part number and relevant specifications against the original equipment documentation before selecting a replacement. For exact compatible equipment models, refer to the manufacturer's documentation. Do not assume compatibility based on the manufacturer name alone.
TECHNICAL SPECIFICATIONS:
Product Identification:
Brand: Johnson Controls
Part Number: V47AR-2
Component Type: Temperature Actuated Modulating Valve
Material Details:
Body Material: Cast Iron
Operating Conditions:
Action Type: Direct Acting
Temperature Range: 115 to 180°F
Connection Specifications:
Connection Size & Type: 1-1/2" ASME Flange
Sensing Specifications:
Capillary Length: 6 Feet
Bulb Style & Size: Style 4 (11/16" Dia. x 6" Length)
Bulb Fitting: 1/2" NPT External
Step 1: Turn off power and shut off water supply to ensure safety.
Step 2: Remove the old valve from the piping system.
Step 3: Install the new modulating valve in the correct flow direction.
Step 4: Secure connections with proper fittings and tighten to prevent leaks.
Step 5: Connect the temperature actuator and wiring according to the diagram.
Step 6: Restore power and water, then test for proper modulating operation between.