Facebook Pixel

Johnson Controls V47AR-2 Temperature Actuated Modulating Valve 115°F-180°F 1-1/2"

Special Price $1,137.40 Regular Price $1,262.52
In stock
SKU
V47AR-2
The Johnson Controls V47AR-2 Temperature Actuated Modulating Valve is a device element that delivers precise temperature sensing in HVAC systems. It is most suitable where temperature stability is desirable because the valve operates in the range of between 115°F and 180°F. This modulating valve has a unique characteristic of changing flow rates so that it can only maintain a constant thermal control on the medium that it regulates by its temperature. It is usually installed into heating and cooling systems since comfort and efficiency depend on stability and temperature control.
https://www.partshnc.com/media/catalog/product/v/4/v47ar-2.jpg

Specifications

  • Temperature Range: 115°F to 180°F
  • Pipe Connection Diameter: 1-1/2"
  • Material: Stainless Steel
  • Weight: 15.13lbs

PRODUCT OVERVIEW:
Temperature actuated water regulating valves manage cooling liquid flow using remote thermal sensing. The Johnson Controls V47AR-2 Temperature Actuated Modulating Valve is an OEM component designed to provide automatic flow control in compatible water-regulated systems. Operating without external electrical power, this direct-acting valve adjusts internal fluid passages as temperature shifts at the sensing bulb. By modulating water throughput across a 115°F to 180°F range, the unit maintains system thermal stability and protects equipment from temperature excursions.

REMOTE THERMAL SENSING:
Thermal fluid expansion inside the remote sensing bulb drives internal valve positioning through an armored capillary tube. As temperature rises at the sensing bulb, expanding liquid generates hydraulic force that travels down the capillary line to position the valve seat. The direct-acting mechanism opens further under higher heat loads to allow maximum cooling water flow through the 1-1/2" valve body. When temperatures drop back toward setpoint, internal spring force balances the fluid pressure to throttle water throughput.

HEAVY-DUTY FLOW REGULATION:
Constructed with a heavy-duty cast iron body, the valve provides long-term structural durability in continuous fluid handling applications. The internal direct-acting mechanism connects to the thermal element, modulating water passage across the 1-1/2" ASME flanged connection ports. This self-contained assembly maintains precise flow regulation strictly in response to thermal conditions at the 1/2" NPT bulb mounting point, ensuring steady operation under fluctuating equipment loads.

REPLACEMENT GUIDELINES:
Component replacement is necessary when the valve fails to adjust water flow, displays seat binding, or suffers capillary charge loss. Malfunctioning temperature regulating valves compromise system performance by causing temperature overshooting, inadequate heat dissipation, or continuous fluid waste. Qualified technician assistance is recommended for hydronic line piping, pressure testing, and thermal bulb installation. Before purchasing, verify the part number and all relevant specifications against the original equipment documentation to ensure the replacement matches the system requirements.

COMMON FAILURE SYMPTOMS:

  • System fluid temperature overshoots or undershoots the target 115°F to 180°F operating setpoint.
  • Internal valve disc sticks or binds, failing to modulate water flow during thermal cycles.
  • Cooling water leaks continuously around the cast iron body housing or 1-1/2" ASME flanged joint connections.
  • Kinked, severed, or leaking 6-foot capillary tubing resulting in total loss of thermal actuation force.

EQUIPMENT COMPATIBILITY:
The Johnson Controls V47AR-2 is intended for compatible water and heating equipment requiring a 1-1/2" ASME flanged direct-acting temperature regulating valve with a Style 4 bulb and a 115°F to 180°F temperature range. Confirm the part number and relevant specifications against the original equipment documentation before selecting a replacement. For exact compatible equipment models, refer to the manufacturer's documentation. Do not assume compatibility based on the manufacturer name alone.

TECHNICAL SPECIFICATIONS:
Product Identification:
Brand: Johnson Controls
Part Number: V47AR-2
Component Type: Temperature Actuated Modulating Valve
Material Details:
Body Material: Cast Iron
Operating Conditions:
Action Type: Direct Acting
Temperature Range: 115 to 180°F
Connection Specifications:
Connection Size & Type: 1-1/2" ASME Flange
Sensing Specifications:
Capillary Length: 6 Feet
Bulb Style & Size: Style 4 (11/16" Dia. x 6" Length)
Bulb Fitting: 1/2" NPT External

Write Your Own Review
You're reviewing:Johnson Controls V47AR-2 Temperature Actuated Modulating Valve 115°F-180°F 1-1/2"
Your Rating
Customer Questions
What maintenance is required for the Johnson Controls V47AR-2 Actuated Modulating Valve?

Regularly inspect the valve for leaks, corrosion, and proper movement of internal components. Clean any debris that may restrict flow and verify temperature response accuracy. Routine maintenance ensures consistent modulation performance. Always isolate the system and relieve pressure before servicing.

What are common issues with the Johnson Controls V47AR-2 Actuated Modulating Valve?

  • Valve sticking or failing to modulate properly.
  • Inaccurate temperature response or delayed actuation.
  • Internal scaling or debris causing restricted flow.
  • Leaks from seals or valve body.
  • Wear of internal components affecting performance.

What is the primary function of the Johnson Controls V47AR-2 valve?

The valve automatically modulates water flow based on sensed system temperature to maintain a target thermal setpoint between 115°F and 180°F.

Does the Johnson Controls V47AR-2 require an external electrical power supply?

No, the self-powered assembly utilizes liquid thermal expansion within the sensing bulb and capillary tube to move the valve seat mechanically.

What connection size and mounting fittings are featured on the V47AR-2 assembly?

The main cast iron body features a 1-1/2" ASME flanged connection, while the Style 4 sensing bulb includes a 1/2" NPT external mounting fitting.

What failure signs indicate that a temperature actuated modulating valve needs replacement?

Key indicators include fluid temperatures drifting out of setpoint range, internal valve binding, leaks around body joints or flanges, or damaged capillary tubing.

What steps should be completed prior to replacing a flanged temperature control valve?

Verify part numbers and temperature ranges in equipment manuals, isolate and drain the fluid line, and ensure proper flange gasket sealing during installation.

Installation Steps

Step 1: Turn off power and shut off water supply to ensure safety.

Step 2: Remove the old valve from the piping system.

Step 3: Install the new modulating valve in the correct flow direction.

Step 4: Secure connections with proper fittings and tighten to prevent leaks.

Step 5: Connect the temperature actuator and wiring according to the diagram.

Step 6: Restore power and water, then test for proper modulating operation between.